Skip to Content
Search
Your Cart
Loading...
Categories
Loading...
Home Search 0 Wishlist

Kv value calculator

Calculate the Kv value, the flow rate or the pressure drop of a valve for liquids, gases and saturated steam.

kg/m³
kg/Nm³
kg/h
m³/h
bar
bar
bar
°C
°C

Result

Required Kv value m³/h
Recommended Kvs (30 % reserve) m³/h
Cv value US gal/min
Flow rate Q m³/h
Flow rate Q l/min
Standard flow rate Qn Nm³/h
Standard flow rate Qn Nl/min
Mass flow G kg/h
Pressure drop Δp bar
Outlet pressure p2 bar
Saturated steam temperature (approx.) °C

Flow characteristic

Pressure drop [bar]Flow rate [m³/h]

Critical (choked) flow: the outlet pressure is at most half the absolute inlet pressure. The flow no longer depends on the outlet pressure.

Enter all values to see the result.

The outlet pressure must be lower than the inlet pressure.

This flow rate cannot pass through the valve at the given inlet pressure - the Kv value is too small.

About the calculation

The Kv value is the water flow in m³/h through a valve at a pressure drop of 1 bar. The calculation uses the common practice formulas for liquids, gases and steam, with a separate branch for critical flow. For steam, the saturation temperature is estimated from the inlet pressure unless you enter a temperature.

Not covered: highly viscous media, cavitation, flashing liquids and two-phase flow.

Send us an inquiry with this calculation

We receive your values and results together with your message and get back to you with a suitable product or an offer.

Inputs
Result
Message

            

Thank you. We have received your inquiry and will get back to you shortly.

All results are non-binding guide values based on simplified practice formulas. They do not replace a detailed design by a specialist. Liability for the results is excluded.

Need support with your design? Contact our team - we are happy to help.